Specifications
 
  Environment
Ambient Operating Temperature 0º to 40ºC 0º to 50ºC with derating
Cooling method Forced convection
Humidity 95% maximum non-condensing at 40ºC
Storage Temperature -40º to 50ºC
Altitude 0 to 3000m. Derate 1% per 100m between 1000m and 3000m
Vibration Tested in accordance with IEC 68-2-34 Mechanical Shock In accordance with IEC 68-2-27
Enclosure IP 20 (NEMA1), IP 54 (NEMA12) through panel mounting
Electromagnetic Immunity In compliance with IEC801 and EN50082-2, and complies with EN61800-3 with built-in filter
Electromagnetic Emissions In compliance with EN50081-2 when the recommended RFI filter is used and EMC installation guidelines are followed
 
  AC Supply Requirements
Voltage 200 to 240 VAC ±10%
380 to 480 VAC ±10%
500 to 575 VAC ±10%
500 to 690 VAC ±10%
Phase
Phase Imbalance Tolerance 2% negative phase sequence (equivalent to 3% voltage imbalance between phases)
Frequency 48 to 65 Hz
Input Displacement Power Factor
0.93
 
  Control
Switching Frequency 3, 4, 6, 8, 12, 16 kHz
Output Frequency 0 to 3000 Hz (Open loop)
Output Speed 0 to 40,000 rpm (Closed loop)
Frequency Accuracy ±0.01% of full scale
Frequency Resolution 0.001 Hz
Analog Input Resolution 16 Bit + sign (Qty 1),10 Bit + sign (Qty 2)
Serial Communications 2 or 4-wire RS232 or RS485. Protocol is ANSI x 3.28-2.5-A4, or Modbus RTU
Baud rate 300 to 115,200
Braking DC injection braking (stopping and holding) standard. Dynamic braking transistor standard
Mains Dip Ride Through Up to 1 second depending on inertia and decel time
 
  Protection
DC Bus Undervoltage Trip 175 / 350 / 435 VDC
(approximately 124 / 247 / 307 VAC line voltage)
DC Bus Overvoltage Trip 415 / 830 / 990 VDC
(approximately 293 / 587 / 700 VAC line voltage)
MOV Voltage 160 Joules, 1400 VDC clamping
Transient Protection (Line to line and line to earth) Drive Overload Trip Current overload value is exceeded. Programmable for Normal Duty or Heavy Duty, Open loop or Closed loop operation
Instantaneous
Overcurrent Trip
225% of drive rated current Overcurrent Trip
Phase Loss Trip DC bus ripple threshold exceeded
Overtemperature Trips Drive heatsink, control board, and option module(s) monitoring
Short Circuit Trip Protects against output phase to phase fault
Earth Fault Trip Protects against output phase to ground fault
Motor Thermal Trip Electronically protects the motor from overheating due to loading conditions
 
  Approvals & Listings
UL, cUL Listed E171230
IEC Meets IEC Vibration, Mechanical Shock and Electromagnetic Immunity Standards
CE Designed for marketing
NEMA NEMA 1 enclosure type
VDE Meets VDE Electromagnetic Emmissions Standards
ISO9001: 2000 Certified Manufacturing Facility
ISO 14001 Certified Manufacturing Facility